1、接觸式溫度檢測儀表(水銀溫度計、雙金屬溫度計、壓力式溫度什、熱電阻、熱電偶等)的測溫元件應安裝在能準確反映被測對象溫度的地方。
2、在多粉塵的部位安裝測溫元件,應采取防止磨損的保護措施。
3、測溫元件安裝在易受被測物料強烈沖擊的位置,以及當水平安裝時其插入深度大于1M或被測溫度大于700°C時,應采取防彎曲措施。
4、表面溫度計的感溫面應與被測對象表面緊密接觸,固定牢固。
5、壓力式溫度計的溫包必須全部浸入被測對象中,毛細管的敷設應有保護措施,其彎曲半徑不應小于50MM,周圍溫度變化劇烈時應采取隔熱措施。
1. The temperature measuring element of the contact temperature measuring instrument (mercury thermometer, bimetal thermometer, pressure temperature, thermal resistance, thermocouple, etc.) shall be installed in a place that can accurately reflect the temperature of the measured object.
2. When installing temperature measuring components in dust-prone areas, protective measures against wear shall be taken.
3. The temperature measuring element shall be installed in a position vulnerable to strong impact of the material under test, and anti-bending measures shall be taken when the insertion depth is more than 1M or the measured temperature is more than 700°C during horizontal installation.
4. The temperature sensitive surface of the surface thermometer should be in close contact with the surface of the object to be measured and fixed firmly.
5. The temperature package of pressure thermometer must be immersed into the object under test, and the capillary should be laid with protective measures. Its bending radius should not be less than 50MM.